* * * * * We Serve Better * * * * *

 

 

XLPE INSULATED POWER CABLES
CV. 600 V. Acc to JIS.3606
Size : (1 x 2.5 ................ 500 mm2 )
        ( 2 x 2.5 ................ 300 mm2 )

 

Number
of
Cores.
Size
Conductor
Insulation
Thicness
Jacket
Thicness
Approx.
Overall
Dia.
Approx.
Net.
Weight
Standard
Reel
Length
Delivery
Form
Construction
No. of wire
(x)
mm2
-
-
mm
mm
mm
kg/km.
m.
-
1
2.5
re ( rm )
1 (7)
0.8
1.5
6.3
67
500
DRUM
4
re ( rm )
1 (7)
0.8
1.5
6.8
86
500
6
re ( rm )
1 (7)
1.0
1.5
7.7
116
500
10
re ( rm )
1 (7)
1.0
1.5
8.5
163
500
16
( rm )
7
1.0
1.5
10.0
234
500
25
( rm )
7
1.2
1.5
11.8
331
500
35
( rm )
19
1.2
1.5
12.9
432
500
50
( rm )
19
1.5
1.5
15.0
599
500
70
( rm )
19
1.5
1.5
16.5
782
500
95
( rm )
19
2.0
1.5
19.2
1072
500
120
( rm )
37
2.0
1.5
20.9
1267
500
150
( rm )
37
2.0
1.6
22.6
1615
500
185
( rm )
37
2.5
1.7
25.6
2006
500
240
( rm )
61
2.5
1.8
28.4
2596
500
300
( rm )
61
2.5
1.9
30.9
3179
500
400
( rm )
61
2.5
2.0
34.1
4029
500
500
( rm )
61
3.0
2.2
38.4
5151
500