* * * * * We Serve Better * * * * *

 

 

TABLE : 13
LOW VOLTAGE CABLE
TYPE : NYY - 0.6/1 kV. SII. 0210-78 (SPLN. 43 - 1 : 1981)
(PVC Insulated and Sheathed)
Size : 1 x 1.5 .................. 500 mm 2
MECHANICAL CHARACTERISTICS

 

Size
Resistance at. 200C
Current Carrying Capacity Resistance per - Conductor
Short Circuit Current at 1 sec
Test Voltage
Conductor
Insulation
In Ground
In Air
DC.Calculated
-
300C
300C
mm2
Ohm/km
M.Ohm.km
A
A Ohm / Km
kA
kV/5 min
000 000 000
1.5
11.9
62
*33
*26
-
0.17
4
2.5
7.14
57
*45
*35
-
0.29
4
4
4.47
52
*58
*46
-
0.46
4
6
2.97
44
*47
*58
-
0.70
4
10
1.77
36
*98
*80
-
1.16
4
16
1.12
26
98/107
86/100
0.110/0.254
1.86
4
25
0.708
26
125/138
120/135
0.107/0.242
2.91
4
35
0.514
22
151/165
145/170
0.097/0.228
4.07
4
50
0.379
22

178/196

180/205
0.096/0.189
5.81
4
70
0.262
19
218/240
225/260
0.094/0.210
8.14
4
95
0.189
18
263/289
280/320
0.091/0.203
11.05
4
120
0.150
16
298/329
330/375
0.088/0.196
13.95
4
150
0.122
16
338/374
380/430
0.086/0.192
17.44
4
185
0.0972
16
383/418
440/490
0.086/0.184
21.51
4
240
0.0740
16
436/481
530/590
0.082/0.174
27.91
4
300
0.0590
15
490/552
610/680
0.082/0.170
34.88
4
400
0.0461
14
579/632
740/920
0.078/0.163
46.51
4
500
0.0366
14
659/730
860/960
0.078/0.157
58.14
4

MECHANICAL CHARACTERISTICS || back to top